top of page
GENERAL
Transformer type2 winding toroidal isolation transformer
Construction methodSpecial vibration isolated mounting of transformer
Cooling methodTemperature controlled gradually regulated forced air cooling above 60° transformer core
WINDING DATA
Rated power3.6 kVA
Nominal current16 A / 32 A
Inrush currentSoftstart included <4 A per unit
TappingsPrim/sec. mid-point (110 VAC)
Material windingCopper
Temperature rise classClass F 100 K
Insulation classClass H 180 C
Insulation levelClass AC3
ImpedanceSecundary less than 3.0% at 3.6 kVA
GENERAL DATA
No load consumption21 W per unit
Full load efficiency>95%
Ambient operating temperature-10°C .. + 45°C, derating to 80°C
Storage temperature-25°C to 85°C
Operating humidity95% max, non-condensing
Audible noise<40.0 dB(A); <50 dB(A) with forced cooling
Local user interfaceNone
PROTECTIONS
Overcurrent, short circuitNot included, external breaker(s) required according to local regulations
Temperature protectionAutomatic switch off if transformer core > 120°C
Overvoltage protectionSoftstart is protected for overvoltage using fuse
Earthscreen between windingsCompliant to ABYC, can carry full fault current
SafetyStandards IEC 60079, IEC 60726
MECHANICAL
Protection degreeIP21
Connections input/output6 mm 2 max.
Cable gland entry22 mm
Dimensions (HxWxD)380 x 290 x 208 mm per unit
Mounting holesM8
Weight28.6 Kg per unit
Enclosure constructionAluminum sheet metal
Surface finishingRAL9010 white + AE80104123621 black

Whisper Power WP-GI 3600 Compact Galvanic Isolation-transformer

THB 0.00Price
    • Line
    • Whatsapp
    • Follow us on Facebook
    • Instagram

    ©2026 by Cirrus Group